Calibration (6000 Watt only)

SCPI

To access calibration mode via remote interface, use the command:
CAL:STAT ON, "0000"
To check if the power supply is in calibration mode, use the command:
CAL:STAT ?
1. where the parameter "0000" may be replaced with your own 4-digit security
code.
B–4
ANLG V PGM 10V: Calibrate 10V analog programming interface for setting
voltage output.
ANLG V RB 10V: Calibrate 10V analog programming interface for
monitoring voltage output.
ANLG I PGM 10V: Calibrate 10V analog programming interface for setting
current output.
ANLG I RB 10V: Calibrate 10V analog programming interface for
monitoring current output.
Factory Cal: Lets you restore the factory calibration constants.
Change Code: Lets you change the password code.