Analog Programming Interface Voltage Readback Calibration

1. Attach a DVM across the voltage readback lines, Pins B5 and B1(GND).
2. Enter 5V analog voltage readback calibration menu
3. Minimum calibration level
4. Enter voltage data
5. Maximum calibration level
6. Enter voltage data
7. Power supply calculates and stores calibration constants.
8. The menu will go to the 5V analog current programming calibration menu.

Analog Programming Interface Current Programming Calibration

1. Connect the power source across the current programming lines, Pins B4 and
2. Enter 5V analog current programming calibration menu
3. Minimum calibration level
4. Enter voltage data
5. Maximum calibration level
6. Enter voltage data
TM-XDOP-01XN
Select ANLG V PGM 5V from the calibration menu. Press ENTER.
You will be prompted to set up for output voltage calibration. Press ENTER
when ready.
The power supply will automatically set the voltage readback lines to
approximately 10% of full scale.
Enter the voltage across the voltage readback lines, read from the external
DVM. Press ENTER
The power supply will automatically set the voltage readback lines to
approximately 90% of full scale.
Enter the voltage across the voltage readback lines, read from the external
DVM. Press ENTER.
B1(GND). Attach a DVM across the current programming lines as well.
Select ANLG I PGM 5V from the calibration menu. Press ENTER.
You will be prompted to set up for calibration. Press ENTER when ready.
Set the input to the programming lines to approximately 0.5V (10% of full
scale).
Enter the voltage at the current programming lines, read from the external
DVM. Press ENTER
Set the input to the programming lines to approximately 4.5V (90% of full
scale).
Enter the voltage at the current programming lines, read from the external
DVM. Press ENTER.
Front Panel Calibration Procedure
B–9