Measurement In Ungrounded Single-Phase Split-Phase Networks - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
7.6.2.10

Measurement in Ungrounded Single-Phase Split-Phase Networks

The "4-Wire Wye" ("4-W") topology is available in WAGO-I/O-Check for voltage
measurement.
This topology is fixed in firmware versions 04 and below and selectable in
WAGO-I/O-Check in firmware versions 05 and above.
The voltage transformer ratio can be parameterized in firmware versions 05 and
above and WAGO-I/O-Check versions IO-3.18.1 (CS0609) and above.
This measurement circuit is used in all ungrounded single-phase networks with
an additional center tap as a neutral conductor and with various types of load
connection.
The voltage measurement is performed via voltage transformers (VTs). Voltages
u
and u
L1
L3
calculates voltage u
The current measurement is performed via current transformers (CTs) or
Rogowski Coils.
The measured values of unconnected voltage and current measurement inputs
have no significance.
The voltage transformer ratio and current transformer ratio must be taken into
account for the correct calculation of all values in the process image.
The nominal input voltage is:
- u
= 200 V
LN
Voltage" setting
- u
= 400 V
LN
Voltage" setting
Parameter 47 is used for the setting.
are measured. From the measurement results, the I/O module first
and then voltages U
L2
if a voltage ≤ 120 V
RMS
if a voltage > 120 V
RMS
Connect Devices 153
, U
and U
.
L1
L2
L3
is parameterized for the "Secondary
RMS
is parameterized for the "Secondary
RMS
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents