Table 70: Register 35 - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

84
Process Image
The transformation ratio is set either with WAGO-I/O-CHECK or in registers
39 ... 42. In the process, the divisor for the current transformer ratio (D-CTR) is
set in the registers. Corresponding to the examples above, these would be:
750-495/040-000 (1A):
750-495/040-001 (5A):
This yields the following calculation of the measured values for the current-
dependent variables:
Current
Register 32,
bits 12 ... 15
Registers 39 ... 42
(D-CTR)
Process value
PI scaling factor
Formula
Measured value
current
Active power
Register 32,
bits 12 ... 15
Registers 39 ... 42
(D-CTR)
Process value
PI scaling factor
Formula
Measured value for
power
Active energy
Register 32,
bits 12 ... 15
Registers 39 ... 42
(D-CTR)
Register 35*
Process value
PI scaling factor
Formula
Measured value for
energy
*)
Register 35: The setting in the register defines the PI scaling factor for energy values
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
CTR = 1:45,
CTR = 1:40,
750-495/040-000
1
0x002D (45)
0x0005E250 (385616)
0.0001 A
Measured value = process value × PI scaling factor
38.562 A
750-495/040-000
1
0x002D (45)
0x000049B5 (18869)
0.01 W
Measured value = process value × PI scaling factor
188.69 W
750-495/040-000
1
0x002D (45)
)
2
0x00000D86 (3462)
0.1 Wh
Measured value = process value × PI scaling factor
346.2 Wh
WAGO-I/O-SYSTEM 750 XTR
D-CTR = 45
=> registers
39 ... 42
D-CTR = 40
=> registers
39 ... 42
750-495/040-001
1
0x0028 (40)
0x0003C9D1 (248273)
0.0005 A
124.137 A
750-495/040-001
1
0x0028 (40)
0x0001C3F8 (115704)
0.05 W
5785.20 W
750-495/040-001
1
0x0028 (40)
4
0x00002CA3 (11427)
50 Wh
571350 Wh

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents