Table 71: Register 36; Table 72: Register 37; Table 73: Register 38; Table 74: Register 39 - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V

Table 71: Register 36

0:
≥ 1:

Table 72: Register 37

Undervoltage limit, phase 2,
0:
≥ 1:

Table 73: Register 38

Undervoltage limit, phase 3,
0:
≥ 1:

Table 74: Register 39

Divisor for the current transformer ratio, phase 1,
Activation via register 32, bit 12 required
0:
≥ 1:

Table 75: Register 40

Divisor for the current transformer ratio, phase 2,
Activation via register 32, bit 13 required
0:
≥ 1:
Register 36 – Undervoltage Limit Phase 1
Function
Undervoltage limit, phase 1,
Resolution: 0.1 V
The undervoltage limit check is deactivated.
Value of the undervoltage limit.
Register 37 – Undervoltage Limit Phase 2
Function
Resolution: 0.1 V
The undervoltage limit check is deactivated.
Value of the undervoltage limit.
Register 38 – Undervoltage Limit Phase 3
Function
Resolution: 0.1 V
The undervoltage limit check is deactivated.
Value of the undervoltage limit.
Register 39 – Current Transformer Ratio Phase 1
Function
-not permitted-
Value for the current transformer ratio divisor.
Register 40 – Current Transformer Ratio Phase 2
Function
-not permitted-
Value for the current transformer ratio divisor.
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Appendix 291
Factory Setting
0x0000 (0 V)
Factory Setting
0x0000 (0 V)
Factory Setting
0x0000 (0 V)
Factory Setting
0x0001
Factory Setting
0x0001