750-495/040-00x 3-Phase Power Measurement Module 690 V
Pos : 96 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 2/Spannungs mes sung - Ü bersc hrift 2 @ 13\mod_1346248367139_21.doc x @ 102097 @ 2 @ 1
7.5

Voltage Measurement

Pos : 97 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Anschl uss beispi ele/Anal ogei ngäng e/Spannungs mess ung 750- 0495, 750-0495/040-00x @ 16\mod_1376384543239_21.doc x @ 128572 @ @ 1
Take additional protective measures for voltages on the N connection that
are dangerous if touched
Voltages up to the nominal input voltage of the I/O module (U
measured directly if it is ensured that no voltage to ground that is dangerous if
touched can exist on the N connection of the I/O module during normal
operation. If this is not ensured, additional protective measures must be taken
(e.g., use of voltage transformers with basic insulation).
Otherwise, touch-proof protection from the system may no longer be given in the
event of a fault. This can cause electric shock or burns.
For voltages above the nominal input voltage, use voltage transformers
It is essential to use voltage transformers (VTs) to measure voltages above the
nominal input voltage of the I/O module (U
must be selected in such a way that the secondary voltages of the transformers
do not exceed the nominal input voltage of the I/O module.
Furthermore, the N connection on the module side must be grounded.
For line voltages U
insulation is required.
Otherwise, touch-proof protection from the system may no longer be given in the
event of a fault. This can cause electric shock or burns.
Use safety fuses in voltage paths
Use safety fuses in the voltage paths. Otherwise, bodily injury or property
damage may occur in the event of polarity reversal of the voltage and current
inputs.
Do not confuse the current and voltage connections
When connecting, be sure not to confuse the current and voltage paths, since
direct connection of the line voltages to the low-impedance current inputs will
destroy the I/O module.
> 400 V
, use of voltage transformers with reinforced
LN
RMS
Connect Devices 101
/U
LN
/U
). The voltage transformer ratio
LN
LL
) can be
LL
Manual
Version 1.2.0