WAGO 750-495/040-00 Series Manual page 191

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
"Energy" Tab
On the "Energy" tab, you can adjust or reset the energy values for each phase
after entering the password.
The initial password is "wago". After the first use, please change this password
using [Change password].
If you have forgotten the password, you can uninstall and reinstall the plug-in for
the 3-Phase Power Measurement Module. This resets the password to the initial
password.
The I/O module counts the Energy consumption and saves the values
cyclically. However, with the [Save] and [Delete] commands, you can save
the energy consumption prematurely or reset it to 0.
You can also set the Power meters to a particular value, i.e. pre-populate
them, by selecting the meter in question, entering a value in milliwatt hours
and clicking [Save]. After this is set, the energy metering starts from this
value setting. 15 meters can be selected:
Active energy import, Lx; Active energy export, Lx; Reactive energy,
inductive, Lx; Reactive energy, capacitive, Lx; and Apparent energy, Lx.
See also: tab 4 in "Appendix" > "Tab Assignment".
The following sum meters cannot be selected: Active energy Lx; Active
energy, total; Active energy import, total; Active energy export, total;
Reactive energy, total; Reactive energy, inductive, total; Reactive energy,
capacitive, total; and Reactive energy, Lx. To pre-populate or delete these,
you must select and set the individual components. For example, for active
energy, L1, these would be: Active energy import, L1 and Active energy
export, L1.
These actions are performed immediately and cannot be reverted. Therefore, the
[Save] button at the bottom of the window is disabled.
Commissioning 191
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents