290 Appendix
Table 69: Register 32
Bit 9: Activation of automatic reset of min/max values for phase 2
0:
1:
Bit 10: Activation of automatic reset of min/max values for phase 3
0:
1:
Bit 11: Activation of the Tamper Detect diagnostics
0:
1:
Bit 12: User scaling (current converter ratio), phase 1
0:
1:
Bit 13: User scaling (current transformer ratio), phase 2
0:
1:
Bit 14: User scaling (current transformer ratio), phase 3
0:
1:
Bit 15: User scaling (current transformer ratio), neutral conductor
0:
1:
Table 70: Register 35
Scaling factor for energy values
0:
1:
2:
3:
4:
5:
6:
≥ 7:
-not permitted-
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
Register 32 – Feature Register
Function
Feature Register
Automatic deletion of minimum and maximum current, voltage and power values is
not activated (factory settings).
Automatic deletion of minimum and maximum current, voltage and power values is
activated.
Automatic deletion of minimum and maximum current, voltage and power values is
not activated (factory settings).
Automatic deletion of minimum and maximum current, voltage and power values is
activated.
Tamper Detect diagnostics are activated (factory setting).
Tamper Detect diagnostics are deactivated.
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
User scaling is deactivated; the transformation ratio is 1:1 (factory setting).
User scaling is active; the transformation ratio is 1: (divisor for the current
transformer ratio).
Register 35 – Scaling Factor for Energy Values
Function
750-495/040-000, 750-495/040-002
1 mWh/VARh/VAh
0.01 Wh/VARh/VAh
0.1 Wh/VARh/VAh
1 Wh/VARh/VAh
0.01 kWh/VARh/VAh
0.1 kWh/VARh/VAh
1 kWh/VARh/VAh
WAGO-I/O-SYSTEM 750 XTR
Data Type
Access
Flags
R/W
Data Type
Access
UINT
R/W
0.05 kWh/VARh/VAh
Factory Setting
0x0000
Factory Setting
0x0004
750-495/040-001
5 mWh/VARh/VAh
0.05 Wh/VARh/VAh
0.5 Wh/VARh/VAh
5 Wh/VARh/VAh
0.5 kWh/VARh/VAh
5 kWh/VARh/VAh