Figure 46: Connection Schematic For Ungrounded 3-Phase Network Without Neutral Conductor For Power Measurement With The 3-Wattmeter - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

174 Connect Devices
Figure 46: Connection Schematic for Ungrounded 3-Phase Network without Neutral Conductor for
Power Measurement with the 3-Wattmeter Method for U
U
LL
Table 53: Legend for the Figure "Connection Schematic for Ungrounded 3-Phase Network without
Neutral Conductor for Power Measurement with the 3-Wattmeter Method for
U
LN
No. Explanation
1
Generator:
Generator or transformer in Y connection, without grounding or with defined
ground impedance (ZE)
2
Generator:
Generator or transformer in ∆ connection, without grounding
3
Loads with impedances (Zx):
- Load connection: in ∆ connection
- Load type: symmetrical or asymmetrical
4
Loads with impedances (Zx):
- Load connection: in Y connection
- Load type: symmetrical or asymmetrical
Note that an asymmetrical load leads to a star point shift in the load.
5
Connection terminal N:
Reference potential for all voltage inputs and differential current inputs
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
≤ 600 V
RMS
* ≤ 346 V
and U
≤ 600 V
RMS
LL
WAGO-I/O-SYSTEM 750 XTR
* ≤ 346 V
LN
"
RMS
and
RMS

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents