Input Data; Definition Of The Status Words - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
5.3

Input Data

The input data is transmitted from the I/O module to the fieldbus
coupler/controller. This data consists of 4 status words and eight data words
(process values 1 ... 4).
5.3.1

Definition of the Status Words

Status word
Bit 7
COM
COM
ERROR
ERR_BK
ERR_L3
ERR_L2
ERR_L1
Bit 6
Bit 5
ERROR
-
Communication mode:
0 = process data communication
1 = register communication
General error:
0 = OK
1 = general error (one or more ERR_* bits are set)
Group error, I/O module
0 = OK
1 = error occurred
Group error, phase L3
0 = OK
1 = error occurred
Group error, phase L2
0 = OK
1 = error occurred
Group error, phase L1
0 = OK
1 = error occurred
Byte 0
Bit 4
Bit 3
Bit 2
-
ERR_BK ERR_L3 ERR_L2 ERR_L1
Process Image
63
Bit 1
Bit 0
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents