Energy" Tab; Figure 76: "Energy" Tab - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
8.4.3

"Energy" Tab

On the "Energy" tab, you can adjust or reset the energy values for each phase
after entering the password.
The initial password is "wago." After the first use, please change this password
using [Change password].
If you have forgotten the password, you can uninstall and reinstall the plug-in for
the 3-Phase Power Measurement Module. This resets the password to the initial
password.
The I/O module counts the Energy consumption and saves the values
cyclically. However, with the [Save] and [Delete] commands, you can save
the energy consumption prematurely or reset it to 0.
You can also set the Power meters for total active energy and total
reactive energy to a particular value, i.e. pre-populate them, by selecting
the meter in question, entering a value in milliwatt hours and clicking
[Save]. After this is set, the energy metering starts from this value setting.
These actions are performed immediately and cannot be reverted. Therefore, the
[Save] button at the bottom of the window is disabled.

Figure 76: "Energy" Tab

Commissioning 219
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents