Table 57: Description Of Marking Example According To Atex And Iecex - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V

Table 57: Description of Marking Example According to ATEX and IECEx

Marking
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Dust
II
3 D
Ex
tc
IIIC
T135°C
Dc
Mining
I
M2
Ex
d
I
Mb
Gases
II
3 G
Ex
nA
IIC
T4
Gc
Pos : 127.7 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Use in Hazardous Environments 269
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22)
Explosion protection mark
Type of protection: Protection by enclosure
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment group: Mining
Category: High level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Explosion group for electrical equipment for
mines susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2)
Explosion protection mark
Type of protection: Non-sparking equipment
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents