WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
3.6.4
Measured Values
Table 12: Technical Data – Measured Values
Measurement method
Calculated values
Process data updating:
Voltage, Lx - N
Min./max. voltage, Lx - N
Voltage, Lx - Ly
Average value, voltage, Lx - N
Peak value, voltage, Lx - N
Current, Lx
Min./max. current, Lx
Average value, current, Lx
Peak value, current, Lx
Current, N
Active power, Lx
Min./max. active power, Lx
Reactive power, Lx
Apparent power, Lx
Energy meter
Line frequency, Lx
Min./max. line frequency, Lx
Phase angle phi, Lx
cos phi
PF power factor, Lx
LF power factor, Lx
Fundamental vibration/upper harmonic
Initialization times:
Collection changes
HD/THD, current 240 ms
HD/THD, voltage 240 ms
Collections 010 Approx. 1400 ms
Collections 020, 021 and 022 Approx. 1100 ms
RMS value calculation (true RMS) for
voltages and currents, measured value
acquisition at 8 kHz, synchronous on
all 7 measurement inputs, 24 bit
resolution
Line-to-line voltage, power output,
energy, power factors, line frequency,
harmonic analysis up to the 41st
harmonic
40 ms
50 ms
340 ms
Adjustable, 5 s ... 900 s
200 ms
40 ms
50 ms
Adjustable, 5 s ... 900 s
200 ms
40 ms
40 ms
50 ms
340 ms
40 ms
400 ms
280 ms
280 ms
340 ms
340 ms
280 ms
280 ms
Current 240 ms
Voltage 240 ms