WAGO 750-495/040-00 Series Manual page 65

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Expanded status word 1
Bit 7
STAT7
STAT7
STAT6
STAT5
STAT4
STAT3
Bit 6
Bit 5
STAT6
STAT5
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, undervoltage, Lx:
0 = threshold not reached
1 = threshold value underrun
If STAT_SEL = status of I/O module:
- Tamper Detect
0 = error current i
to
Tamper Detect threshold value
1 = error current i
Tamper Detect threshold value
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, overvoltage, Lx:
0 = threshold not reached
1 = threshold reached or exceeded
If STAT_SEL = status of I/O module:
- Rotary field indicator
0 = rotary field correct L1-L2-L3, clockwise
1 = rotary field not correct, counterclockwise
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Threshold value, overcurrent, Lx:
0 = threshold not reached
1 = threshold reached or exceeded
If STAT_SEL = status of I/O module:
- no significance
If STAT_SEL = status of Lx = L1 / L2 / L3:
- status, zero crossings:
0 = signal zero crossings at phase Lx
1 = no zero crossings at phase Lx
If STAT_SEL = status of I/O module:
- no significance
If STAT_SEL = status of Lx = L1 / L2 / L3:
- clipping of voltage signal at Lx:
0 = OK
1 = the voltage signal is outside the measurable
range of the I/O module and has been
limited (clipped).
If STAT_SEL = status of I/O module:
- no significance
Byte 2
Bit 4
Bit 3
STAT4
STAT3
(t) − i
SUM Lx
(t) − i
SUM Lx
Process Image
Bit 2
Bit 1
Bit 0
STAT2
STAT1
(t) is less than or equal
N
(t) is greater than
N