Table 22: Emc - Immunity To Interference - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Pos : 58.5 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Nor men und Richtlini en/EM V-Nor men I/O-M odul 750- xxxx/0040- 0000, nur Standar dversi on - Ei nlei tung XTR @ 18\mod_1395909426189_21.doc x @ 149708 @ @ 1
The I/O module 750-495/040-00x meets the following EMC standards as these
standards relate to the I/O module:
Pos : 58.6 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Nor men und Richtlini en/Nor men Störfestig keit XTR @ 18\mod_1394030613258_21.doc x @ 147348 @ @ 1
Table 22: EMC – Immunity to Interference
Standard
Electrostatic Discharge
• EN 61000-4-2
• EN 60255-26
• IEEE C37.90.3
High-frequency Electromagnetic Fields
• EN 61000-4-3
• EN 60255-26
• IEEE C37.90.2
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• EN 60255-26
• IEEE C37.90.1
Surge Voltage / Surge
• EN 61000-4-5
• EN 60255-26
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
• EN 60255-26
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
• EN 60255-26
Pulse-shaped Magnetic Fields
• EN 61000-4-9
Damped Oscillatory Magnetic Fields
• EN 61000-4-10
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
• EN 60255-26
Damped Sinusoidal Oscillations
• EN 61000-4-12
Harmonics and Interharmonics
• EN 61000-4-13
Conducted Asymmetric Disturbances
• EN 61000-4-16
Test Value
8 kV (contact discharge)
8 kV (air discharge)
20 V/m (80 MHz ... 1 GHz)
10 V/m (1 GHz ... 3 GHz)
4 kV
2 kV (conductor/conductor)
4 kV (conductor/ground)
10 V (150 kHz ... 80 MHz)
300 A/m continuous / 1000 A/m for 1 s
300 A/m
100 A/m
Standard not applicable
2 kV (conductor/conductor)
4 kV (conductor/ground)
Standard not applicable
30 V continuous
300 V for 1 s