Voltage Measurement On 2 Line Conductors - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

134 Connect Devices
7.6.2.1.2

Voltage Measurement on 2 Line Conductors

For voltage measurement, set the topology to "4-Wire Wye, 2-Phase" ("4-W/2-P")
in WAGO-I/O-Check.
This topology is available with firmware versions 05 and above and WAGO-
I/O-Check versions IO-3.18.1 (CS0609) and above.
This measurement circuit is used in all grounded 3-phase networks with a neutral
conductor.
The measurement circuit basically corresponds to the "Grounded 3-Phase
Network with Neutral Conductor for Power Measurement and Voltage
Measurement on 3 Line Conductors for U
connection schematic, but without the voltage measurement of phase L2. This
circuit is used for measuring power in grounded 3-phase networks with a neutral
conductor with only 2 voltage transformers.
Voltage measurement is performed via voltage transformers (VTs). Voltages u
and u
are measured. From the measurement results, the I/O module first
L3
calculates voltage u
The current measurement is performed via current transformers (CTs) or
Rogowski Coils.
The voltage transformer ratio and current transformer ratio must be taken into
account for the correct calculation of all values in the process image.
The nominal input voltage is:
- u
= 200 V
LN
Voltage" setting
- u
= 400 V
LN
Voltage" setting
Parameter 47 is used for the setting.
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
and then voltages U
L2
if a voltage ≤ 120 V
RMS
if a voltage > 120 V
RMS
WAGO-I/O-SYSTEM 750 XTR
> 400 V
and u
LN
RMS
, U
and U
.
L1
L2
L3
is parameterized for the "Secondary
RMS
is parameterized for the "Secondary
RMS
≤ 400 V
"
LN
RMS
L1