162 Connect Devices
The following should be noted in connection with the measurement setup:
- The grounded line conductor must be determined with certainty.
- The grounded line conductor is connected to the N connection of the
I/O module.
For example, in the following connection diagram, L2 is selected as the
grounded line conductor.
- The two other line conductors are connected to voltage measurement inputs
L1 and L3.
- Voltage measurement input L2 is not connected.
- The current transformers are connected according to the order of the line
conductors on the voltage side (for example, L2 is the grounded line conductor
in the following connection diagram).
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
WAGO-I/O-SYSTEM 750 XTR