40
Connect Devices
5.2.3

Analog Inputs

Only connect SELV/PELV voltages!
Only SELV/PELV voltages shall be connected to the device terminals.
Analog inputs are single-ended!
The analog inputs are single-ended and the "Aix–" connections are connected
internally to the "GND" connections.
Connect shielding!
Shielded cables are required for analog inputs. The cable shield must be
connected to the grounded DIN rail (see section "Connections" > "Shielding").
5.2.3.1

Current Measurement

Figure 16: Connection example of transducer with current output at input AI1

761-316 TO-PASS® Mobile, 4 AI, Web, MODBUS
WAGO-TO-PASS® 761
Manual
Version 2.0.0