WAGO 750-495/040-00 Series Manual page 18

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

18
Important Notes
Protect the components against materials having seeping and insulating
properties!
The components are not resistant to materials having seeping and insulating
properties such as: aerosols, silicones and triglycerides (found in some hand
creams). If you cannot exclude that such materials will appear in the component
environment, then install the components in an enclosure being resistant to the
above-mentioned materials. Clean tools and materials are imperative for
handling devices/modules.
Pos : 20.18.4 /Alle Serien (Allgemeine M odul e)/Sic herheits- und s onstige Hinweise/Achtung/Ac htung: R einigung nur mit zul ässigen M aterialien! @ 6\mod_1260181203293_21.doc x @ 46751 @ @ 1
Clean only with permitted materials!
Clean housing and soiled contacts with propanol.
Pos : 20.18.5 /Alle Serien (Allgemeine M odul e)/Sic herheits- und s onstige Hinweise/Achtung/Ac htung: Kei n Kontakts pray verwenden! @ 6\mod_1260181290808_21.doc x @ 46755 @ @ 1
Do not use any contact spray!
Do not use any contact spray. The spray may impair contact area functionality in
connection with contamination.
Pos : 20.18.6 /Alle Serien (Allgemeine M odul e)/Sic herheits- und s onstige Hinweise/Achtung/Ac htung: Ver pol ung en der D aten- und Versorgungsleitungen vermeiden! @ 6\mod_1260184045744_21.doc x @ 46767 @ @ 1
Do not reverse the polarity of connection lines!
Avoid reverse polarity of data and power supply lines, as this may damage the
devices involved.
Pos : 20.18.7 /Alle Serien (Allgemeine M odul e)/Sic herheits- und s onstige Hinweise/Achtung/Ac htung: El ektr ostatisc he Entladung vermei den! @ 6\mod_1260181364729_21.doc x @ 46759 @ @ 1
Avoid electrostatic discharge!
The devices are equipped with electronic components that may be destroyed by
electrostatic discharge when touched. Please observe the safety precautions
against electrostatic discharge per DIN EN 61340-5-1/-3. When handling the
devices, please ensure that environmental factors (personnel, work space and
packaging) are properly grounded.
Pos : 20.19 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en (alte Struktur)/Sic her heits- und s onstige Hi nweis e/Ac htung/Ac htung: XTR - Is olationspr üfung en mit DC durchführen! @ 15\mod_1370843209441_21.doc x @ 122210 @ @ 1
Use only direct current (DC) for insulation testing!
Both the system voltage and field voltage side are capacitively coupled to the
DIN-rail. If an I/O module is mounted on the DIN-rail, application of an AC voltage
between the DIN-rail and at least one of these two potentials can lead to the
destruction of the module.
Use only direct current (DC) for insulation testing. To avoid destroying the I/O
module, you must discharge it completely before applying the test voltage again.
Pos : 21 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
WAGO-I/O-SYSTEM 750 XTR

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents