WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Table 81: Register 46
Storing interval, energy consumption,
0 ... 59:
60 ... 255: Time in seconds up to automatic storage of energy values.
≥ 256:
Table 82: Register 47
Error register for the parameter channel
0:
1:
2:
3:
4:
5:
≥6:
Table 83: Register 48
for energy meter and calibration preset
Table 84: Register 49
for energy meter and calibration preset
Table 85: Register 50
for energy meter and calibration preset
Table 86: Register 51
for energy meter and calibration preset
Register 46 – Storage Interval, Energy Consumption
Function
Resolution: 1 second
-not permitted-
-not permitted-
Register 47 – Error Register for the Parameter Channel
Function
Calibration procedure, no error
Calibration procedure, division by zero
Calibration procedure "Gain" > 2
Calibration procedure, command sequence not followed
Calibration procedure, calibration step not implemented
Calibration procedure, the "period" register in the MCU microcontroller has never
been read before
-not permitted-
Register 48 – Container 1
Function
Container 1,
Register 49 – Container 2
Function
Container 2,
Register 50 – Container 3
Function
Container 3,
Register 51 – Container 4
Function
Container 4,
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Data Type
Access
UINT
R/W
Appendix 293
Factory Setting
0x003C (60s)
Factory Setting
0x0000
Factory Setting
0x0000
Factory Setting
0x0000
Factory Setting
0x0000
Factory Setting
0x0000