Analog Inputs; Current Measurement; Figure 15: Connection Example For A Transducer At Ai1 Input - WAGO -TO-PASS 761 Manual

Telecontrol module compact, 2 ai telecontrol module for fault detection/indication, monitoring and remote control
Hide thumbs Also See for WAGO-TO-PASS 761:
Table of Contents

Advertisement

WAGO-TO-PASS® 761
761-111 Telecontrol Module Compact, 2 AI
5.2.3

Analog Inputs

Only connect SELV/PELV voltages!
Only SELV/PELV voltages shall be connected to the device terminals.
Analog inputs are single-ended!
The analog inputs are single-ended and the "Aix–" connections are connected
internally to the "GND" connections.
Connect shielding!
Shielded cables are required for analog inputs. The cable shield must be
connected to the grounded DIN rail (see section "Connections" > "Shielding").
5.2.3.1

Current Measurement

Figure 15: Connection example for a transducer at AI1 input

Manual
Version 2.0.0
Connect Devices
39