WAGO-TO-PASS® 761
761-111 Telecontrol Module Compact, 2 AI
5.2.3
Analog Inputs
Only connect SELV/PELV voltages!
Only SELV/PELV voltages shall be connected to the device terminals.
Analog inputs are single-ended!
The analog inputs are single-ended and the "Aix–" connections are connected
internally to the "GND" connections.
Connect shielding!
Shielded cables are required for analog inputs. The cable shield must be
connected to the grounded DIN rail (see section "Connections" > "Shielding").
5.2.3.1
Current Measurement
Figure 15: Connection example for a transducer at AI1 input