I/O Module" Tab - WAGO 750-495/040-00 Series Manual

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

188 Commissioning
8.2.3

"I/O Module" Tab

On the "I/O Module" tab, you can configure all 3 general settings, delete
min./max. values and configure the energy measurements. These settings apply
to the entire I/O module.
In "General", select the line frequency of the power supply network and the
phase for which the peak values are to be specified. You can enable a
watchdog. The watchdog disables the green "A" status LED if no process
data is received for 200 ms or more.
For "Min./Max. Values", you can reset a specific minimum or maximum
value by selecting this value in the list field and clicking [Delete]. This action
is performed immediately.
For "Energy", select the desired scaling factor from the list field. The energy
values displayed are then scaled accordingly. Enter the interval for cyclic
energy consumption storage in seconds in the text field.
Finally, you can specify thresholds for the energy measurements (active
power, reactive power and apparent power). This allows you to keep
creepage currents that are inherent to the system from affecting the energy
measurement. The energy measurement is interrupted as soon as there is
an underrun of one of the set values.
See also section "Appendix" > "Parameter Assignment".
With Rogowski version 750-495/040-002, also specify which coils you are using
for measurement: RT500 or RT2000.