300 Appendix
Table 118: Parameter 41 (Supported by Firmware Versions 05 and above)
NOLOAD threshold for reactive power
0:
1 ... 30000:
Table 119: Parameter 42 (Supported by Firmware Versions 05 and above)
NOLOAD threshold for apparent power
0:
1 ... 30000:
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
Parameter 41 – NOLOAD Threshold, Reactive Power
Function
The NOLOAD threshold is disabled (factory setting)
Power threshold as NOLOAD limit value.
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the power
750-495/040-000
750-495/040-001
750-495/040-002 RT500
750-495/040-002 RT2000
750-495/040-002 RC70
750-495/040-002 RC125
750-495/040-002 RC175
750-495/040-002 with user-defined RC: See the following section "Calculation of
the NoLoad Limit for User-Defined Rogowski Coils."
Parameter 42 – NOLOAD Threshold, Apparent Power
Function
The NOLOAD threshold is disabled.
Power threshold as NOLOAD limit value.
Resolution: 0.001 % / LSB (0.001 % to 30.000 %)
The threshold is specified as a % of the full scale of the power
750-495/040-000
750-495/040-001
750-495/040-002 RT500
750-495/040-002 RT2000
750-495/040-002 RC70
750-495/040-002 RC125
750-495/040-002 RC175
750-495/040-002 with user-defined RC: See the following section "Calculation of
the NoLoad Limit for User-Defined Rogowski Coils."
WAGO-I/O-SYSTEM 750 XTR
Data Type
Access
UINT
R/W
P
= 1,014.91 VAR
Fullscale
P
= 4,465.63 VAR
Fullscale
P
= 2,223,038.77 VAR
Fullscale
P
= 2,224,048.33 VAR
Fullscale
P
= 1,977,032.33 VAR
Fullscale
P
= 1,973,632.66 VAR
Fullscale
P
= 1,970,064.91 VAR
Fullscale
Data Type
Access
UINT
R/W
P
= 1,014.91 VA
Fullscale
P
= 4,465.63 VA
Fullscale
P
= 2,223,038.77 VA
Fullscale
P
= 2,224,048.33 VA
Fullscale
P
= 1,977,032.33 VA
Fullscale
P
= 1,973,632.66 VA
Fullscale
P
= 1,970,064.91 VA
Fullscale
Factory Setting
0x0000 (disabled)
Factory Setting