WAGO 750-495/040-00 Series Manual page 155

3-phase power measurement module 690 v for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Figure 39: Connection Schematic for Ungrounded Single-Phase Split-Phase Network for Power
Measurement for U
Table 46: Legend for Figure "Connection Schematic for Ungrounded Single-Phase Split-Phase
Network for Power Measurement for U
No. Explanation
1
Generator:
Generator or transformer in single-phase split-phase connection, without
neutral conductor grounding
2
Current transformer (CT3) for current measurement in the neutral
conductor (optional)
3
Loads with impedances (Zx):
- Load connection: in split-phase connection
- Load type: all variants
4
Connection terminal N:
Reference potential for all voltage inputs and differential current inputs
5
Connection terminal L2:
Connection to the N connection (optional, to avoid erroneous measured
values for the unused phase)
Pos : 100 /Dokumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
U
> 400 V
and u
L1,
L2
RMS
L1,
U
> 400 V
L1,
L2
Connect Devices 155
u
≤ 400 V
L2
RMS
and u
u
≤ 400 V
RMS
L1,
L2
"
RMS
Manual
Version 1.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-495/040-000750-495/040-001750-495/040-002

Table of Contents