3.4

Operating Elements

Pos : 46 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Bedienel emente/Bedi enelemente I/O-Modul 75x- xxxx nicht vorhanden @ 4\mod_1236322031125_21.doc x @ 28063 @ @ 1
The I/O module 750-495/040-00x has no operating elements.
Pos : 47 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 2/Sc hematis ches Sc haltbild - Ü bersc hrift 2 @ 4\mod_1240984441312_21.doc x @ 31967 @ 2 @ 1
3.5

Schematic Diagram

Pos : 48 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Sc hematische Sc hal tbilder/AI/Sc hematisc hes Sc haltbild 750-0495/040- 00x @ 22\mod_1424858436413_21.doc x @ 175754 @ @ 1
Take additional protective measures for voltages on the N connection that
are dangerous if touched
Voltages up to the nominal input voltage of the I/O module (U
measured directly if it is ensured that no voltage to ground that is dangerous if
touched can exist on the N connection of the I/O module during normal
operation. If this is not ensured, additional protective measures must be taken
(e.g., use of voltage transformers with basic insulation).
Otherwise, touch-proof protection from the system may no longer be given in the
event of a fault. This can cause electric shock or burns.
The 3 voltage measuring paths are not electrically isolated from the
4 current measuring paths
The N connection represents the device-internal reference potential for all
electrical measurements.
Additional unintended potential differences between the N connection and the
current connections can lead to incorrect measured values and the destruction of
the I/O module.
The current connections must not be grounded.
Functional ground – FE
To discharge interference, the N connection must be connected to the DIN-rail
via a 2 nF capacitor and a spring contact. To achieve functional grounding, the
DIN-rail must be grounded.

Figure 6: FE Spring Contact

Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
WAGO-I/O-SYSTEM 750 XTR