Process Image
5.6
Examples of the Calculation of the Measured Values
from the Process Values
The format of signed measured values (Int32) is the two's complement.
In general, the following formula applies to the calculation of the measured
values from the process values:
The scaling factor PI is defined for each measured value in the section
"Measured Value Collections." Examples of the calculation follow:
Calculation of the measured values for voltage
Voltage
Process value
PI scaling factor
Formula
Measured value for
voltage
Calculation of the measured values for frequency
Frequency
Process value
PI scaling factor
Formula
Measured value for
frequency
Calculation of the measured values for phase angle
Phase angle
Process value
PI scaling factor
Formula
Measured value for
phase angle
Manual
Version 1.2.0
750-495/040-00x 3-Phase Power Measurement Module 690 V
Measured value = Process value × PI scaling factor
750-495/040-000,
750-495/040-002
0x000007D0 (2000)
0.01 V
Measured value = process value × PI scaling factor
20.00 V
750-495/040-000,
750-495/040-002
0x0000C3B8 (50104)
0.001 Hz
Measured value = process value × PI scaling factor
50.10 Hz
750-495/040-000,
750-495/040-002
0x00004E3 (1251)
0.01 degrees
Measured value = process value × PI scaling factor
12.51 degrees
WAGO-I/O-SYSTEM 750 XTR
750-495/040-001
0x00003D76 (15734)
0.01 V
157.34 V
750-495/040-001
0x0000EB9C (60316)
0.001 Hz
60.32 Hz
750-495/040-001
0x0000226E (8814)
0.01 degrees
88.14 degrees