7 Troubleshooting
7-2

Using the Software Tool

This section shows troubleshooting when using the software tool.
Problems
It is not possible to communicate
with the Main Unit from the software
tool
The measured value is displayed,
but the value at a certain time is
fixed and does not change
7 - 6
Cause
The IP address of the com-
puter is automatically
acquired or fixedly set to a
segment different from the IP
address of the Main Unit.
The IP address setting of the
Main Unit on the project is dif-
ferent from the actual IP
address.
If the external trigger input
turns ON, the measurement
value immediately before the
input turns ON is held and dis-
played.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Possible correction
Set the IP address of the
computer to IP address of
same segment as the
Main Unit.
Reset the IP address of
the target Main Unit on the
Setting K6PM Screen.
Turn OFF the external trig-
ger.