K6Pm-Th Sensor Alarm Setting Object (Class Id: 378 Hex) - Omron K6PM-TH User Manual

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

5 Monitoring and Setting with the EtherNet/IP Communications
5-3-6

K6PM-TH Sensor Alarm Setting Object (Class ID: 378 hex)

This object sets the alarm threshold of the Main Unit.
Service Codes
Service
Service name
code
01 hex
Get_Attributes_All
02 hex
Set_Attributes_All
0E hex
Get_Attribute_Single Reads the value of the specified attribute.
10 hex
Set_Attribute_Single
Class ID
Specify 378 hex.
Instance ID
Specify the following data according to the target.
• For class: Specify 00 hex.
• For instance: Specify 01 to 1F hex (compatible with sensor number 1 to 31).
Attribute ID
Specify the information to write.
 Class Attribute ID
None
 Instance Attribute ID
The instance attribute ID specifies the per-instance attribute.
The setting parameter is enabled after the power supply is reset.
An example of a case where the instance ID is 01 hex is described below.
Attribute ID
64 hex
Sensor 1
Internal temperature alarm
setting (threshold 1)
65 hex
Sensor 1
Internal temperature alarm
setting (threshold 2)
66 hex
K6PM-TH sensor 1 seg-
ment 0
Current temperature alarm
setting (threshold 1)
5 - 20
Reads the values of all attributes.
Write values to all attributes.
Write the value of the specified attribute.
Parameter name
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Description
Description
Attribute
Write
Write
Write
Supported services
Classes
Instances
Not supported
Supported
Not supported
Supported
Not supported
Supported
Not supported
Supported
Data
Default
Data type
value
UINT
01C2 hex
(45.0)
UINT
0226 hex
(55.0)
UINT
02BC hex
(70.0)