1-2-2

Measurement, Monitoring and Output

Types of Measurement Values
The measurement values are of the following types.
• Current temperature per segment of each infrared thermal sensor, or the predicted arrival tem-
perature
• Internal current temperature of each infrared thermal sensor, or the predicted arrival temperature
• Differential temperature between the current temperature of each infrared thermal sensor and the
K6PM-TH sensor internal current temperature
Monitoring (alarms) and Output
• During monitoring (alarm), threshold judgment is first performed for threshold 1 and threshold 2
with respect to each of the above measurement values, and the "individual alarm" is judged.
• Next, the OR logic is obtained for each "individual alarm" and normal, threshold 1 exceeded, or
threshold 2 exceeded is judged for each monitor target as the "comprehensive alarm".
• Finally, the "comprehensive alarm" is displayed on the alarm bar of the Main Unit front-panel and
transistor output is performed.
*1. If the alarm latch is set to "ON", the alarm status of the K6PM-TH comprehensive judgment (such as alarm
bar and transistor outputs 1 and 2) is held. Press and hold the SEG/ALM RST Key on the Main Unit
front-panel to release the latch. Also, the transistor output type of output 1 and output 2 can be set to Normally
closed or Normally open.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)