Omron K6PM-TH User Manual page 80

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

4 Monitoring the Temperature in Control Panel with the Main Unit and the Software Tool
Alarm
Status dis-
bar
play LED
Lit yellow
"ALM" and
"MON" light up
simultane-
ously
Flashing
yellow
(only when the
correspond-
ing K6PM-TH
sensor num-
ber is being
displayed)
Lit red
Flashing
red
Not lit.
"ERR" lit
4 - 4
Product
status
indica-
Status
tion (MS)
LED
Lit green
Comprehensive
alarm: Threshold 1
exceeded
Lit green
Comprehensive
alarm: Arrival pre-
diction threshold 1
exceeded (When
the arrival predic-
tion function is
enabled)
Lit green
Comprehensive
alarm: Threshold 2
exceeded
Lit green
Comprehensive
alarm: Arrival pre-
diction threshold 2
exceeded (When
the arrival predic-
tion function is
enabled)
Lit red
A Main Unit internal error has occurred
This is the state when a Main Unit internal error has occurred.
"8888" flashes on the main numeric display.
Note The alarm bar does not light up when a Main Unit
●Alarm bar
(Green): Comprehensive alarm (normal): Lit
(Yellow): Comprehensive alarm
(Red): Comprehensive alarm (threshold 2 exceeded): Lit,
(Not
lit): Other than the above.
●Status display LED:
"MON" Lit: K6PM sensor monitoring state
"ERR" Lit: Internal device error occurred
"ALM" Lit: An alarm has occurred (only when the corresponding
K6PM sensor number is being displayed)
"AGE" Lit: The running time has reached 100%
Product status indication (MS) LED
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Meaning
There are no "Over threshold 2" results and at
least one "Over threshold 1" result in the mea-
sured values. If the conditions for blinking and
lighting are both met, lighting is given priority.
There is at least one "Over threshold 2" result in
the measured values. If the conditions for blink-
ing and lighting are both met, lighting is given
priority.
internal error occurs.
(threshold 1 exceeded): Lit,
Comprehensive alarm
(arrival prediction threshold 1 exceeded): Flashing
Comprehensive alarm
(arrival prediction threshold 2 exceeded): Flashing

Advertisement