4 Monitoring the Temperature in Control Panel with the Main Unit and the Software Tool
Operation for Releasing the Alarm Latch
The operation performed to release the alarm latch is as described below.
Example: Conditions: When the threshold value is such that threshold 2 > threshold 1, there is an alarm
latch, and there is no arrival prediction
Threshold 2
Threshold 1
Current value
Status display
Transistor output 1
Transistor output 2
SEG/ALM RST Key
4-2-3
Automatic Saving Log Files
Outline
The software tool saves the following data acquired from the Main Unit to be monitored in each sam-
pling cycle in a tab-delimited text file (.txt file).
• Current temperature per segment and maximum temperature per segment
• K6PM-TH sensor internal current temperature and maximum temperature
• Infrared thermal sensor status
• Main Unit status
• Date time
The timing of executing save is "Always", as long as the software tool is operating and the correspond-
ing Main Unit is in the monitoring mode.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Alarm hysteresis
Lit green
Lit yellow
Release the latch
Latch the alarm
Lit red
Press for 5 seconds min. to
release the latch
Lit green
4