Omron K6PM-TH User Manual page 28

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

1 Outline
Symbol
(D)
Numeric LCD display
(E)
SEG
(F)
Status display
(G)
Operation Keys
(H)
Lower terminal
(I)
DIN Track mounting hook
(J)
Communications connec-
tor
1 - 10
Name
Depending on the operating mode, the display differs as shown
below.
• Monitoring mode: Current temperature of the selected segment of
the selected sensor
(a) When communications are not established with the sensor:
"----" is displayed
(b) When a K6PM-TH sensor communications error occurs:
"serr" is displayed
(c) When the sensor temperature exceeds the measurement
range: The current temperature flashes
(d) During measurement interruption due to an external trigger:
The display is fixed as the value immediately before interrup-
tion
(e) K6PM-TH sensor search mode: "on" is displayed for a sensor
that sends a response, and "off" is displayed for a sensor that
sends no response
• K6PM-TH sensor position adjustment mode: "adj" is displayed
• When a Main Unit internal error occurs: "8888" flashes
The segment number or the number of currently-connected infrared
thermal sensors is displayed. Depending on the operating mode, the
display differs as shown below.
• Monitoring mode: The segment number selected by the SEG/ALM
RST Key is displayed. 0 to 15 Sensor internal temperature: 99
• K6PM-TH sensor search mode: The number of infrared thermal
sensors currently connected to the Main Unit is displayed.
• K6PM-TH sensor position adjustment mode: The number of infra-
red thermal sensors currently connected to the Main Unit is dis-
played.
The status of the Main Unit is displayed as follows:
• MON: K6PM-TH sensor monitoring state. The indicator is not lit
during measurement interruption due to an external trigger.
• ALM: Alarm occurrence state (lit only when the corresponding
K6PM-TH sensor number is being displayed)
• AGE: Running time reaches 100%
• ERR: Main Unit internal error
CH Key: Switching of sensor number
SEG/ALM RST Key pressed for less than 5 seconds: Switching of
segment number
SEG/ALM RST Key pressed and held (5 seconds min.): Alarm latch
released (Can be performed only by this operation. The latch cannot
be released by the software tool and communications.)
CH Key and SEG/ALM RST Key simultaneously pressed and held (5
seconds min.): Initialization
(Operation returns to the factory state.)
Connection is established by the Push-In Plus terminal.
• Transistor output 1 to 3
For details, refer to Transistor Output on page 1-12.
Used for mounting to the DIN Track.
Connects the communications cable of the EtherNet/IP network.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Function

Advertisement

Table of Contents
loading

This manual is also suitable for:

K6pm-thmd-eipK6pm-ths3232

Table of Contents