Additional Information
If you have created network symbols, tag set names and tag names in advance with the
CX-Programmer and have the exported file (.CSV), click To/From File at the lower right, select
Import from File.... By doing so, you can omit the following "(1) -1 Tag editing" and "(1) -2 Edit-
ing tag set" below.
Click Edit Tag (T) ... in the Edit Device Parameters Dialog Box to edit tag sets.
To enter tags, there are tabs for Input (Consume) and Output (Produce), but set only the
Input (Consume) tab when connecting the K6PM series. Select the In - Consume Tab and
click New (N) ..., the Edit Tags Dialog Box will be displayed.
Enter the tag name and its size (128 bytes, 380 bytes or 418 bytes), and click Register (R).
As a "tag name", enter the character string for the CPU Unit's I/O memory address or a net-
work symbol (e.g., 100, W100, D0, Input_Signal).
Addresses in the following I/O memory areas can be set.
CIO Area
Holding Area
Work Area
DM Area
EM Area
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
CPU Unit's data area
Bank 0 hex
:
Bank 18 hex
Address (Text to input in Name Field)
0000 to 6143
H000 to H511
W000 to W511
D00000 to D32767
E0_00000 to E0_32767
:
E18_00000 to E18_32767
Appendices