• The size of the internal data (parameter) of the K6PM device must be any one of 128 bytes,
380 bytes, and 418 bytes.
2)-1 Drag a K6PM-TH to the PLC and register it.
2)-2 Click the Edit Tag Sets Button to create input tags with the above sizes.
2)-3 Register the input tag as it is as input tag set.
2)-4 Select the input tag set created in 2)-3 above from the pull-down list.
2)-5 Match the connection I/O type and instance ID of the output tag set.
2)-6 Register the connection.
Connection Allocation to K6PM Device Dialog Box
PLC side tag set
Input tag set
Create a tag that matches any one of
the sizes of 128 bytes, 380 bytes, and
418 bytes of the internal data of the
K6PM device selected on the right, and
set it as the input tag set as it is.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
5 Monitoring and Setting with the EtherNet/IP Communications
Select any one of the tag sets of
128 bytes, 380 bytes, and 418
bytes that you have created.
PLC
Select the output tag set name to be
displayed from below.
• "Input_100-[128Bytes]"
• "Input_101-[380Bytes]"
• "Input_102-[380Bytes]"
• "Input_103-[418Bytes]"
Match the connection
I/O type and instance ID
of the output tag set.
K6PM side tag set
Output tag set
This size is any one of
128 bytes, 380 bytes,
and 418 bytes.
K6PM-TH
5
5 - 5