6 Monitoring and Setting with the Modbus TCP
K6PM-TH Sensor Alarm Setting (Example: Sensor 1 Detailed Param-
eters)
The detailed parameters of sensor 1 are as described below.
The detailed parameters of sensors 2 to 31 are also same as those of sensor 1.
Address
A100 hex
Sensor 1
Internal temperature
alarm value (threshold 1)
A101 hex
Sensor 1
Internal temperature
alarm value (threshold 2)
A102 hex
K6PM-TH sensor 1 seg-
ment 0
Current temperature alarm
setting (threshold 1)
A103 hex
K6PM-TH sensor 1 seg-
ment 0
Current temperature alarm
setting (threshold 2)
A104 hex
K6PM-TH sensor 1 seg-
ment 0
Differential temperature
alarm value (threshold 1)
A105 hex
K6PM-TH sensor 1 seg-
ment 0
Differential temperature
alarm value (threshold 2)
A106 hex
K6PM-TH sensor 1 seg-
ment 1
Current temperature alarm
setting (threshold 1)
A107 hex
K6PM-TH sensor 1 seg-
ment 1
Current temperature alarm
setting (threshold 2)
A108 hex
K6PM-TH sensor 1 seg-
ment 1
Differential temperature
alarm value (threshold 1)
A109 hex
K6PM-TH sensor 1 seg-
ment 1
Differential temperature
alarm value (threshold 2)
:
:
A13E hex
K6PM-TH sensor 1 seg-
ment 15
Current temperature alarm
setting (threshold 1)
6 - 16
Parameter name
(0000 to 270F hex)
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
:
0000 to 270F hex
(0 to 999.9 [Unit: °C or °F])
Data range
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Initial
Number
R/W
value
of bytes
01F4 hex
2
(50.0)
0258 hex
2
(60.0)
0320 hex
2
(80.0)
03E8 hex
2
(100.0)
0320 hex
2
(80.0)
03E8 hex
2
(100.0)
0320 hex
2
(80.0)
03E8 hex
2
(100.0)
0320 hex
2
(80.0)
03E8 hex
2
(100.0)
:
:
0320 hex
2
(80.0)
*1
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
:
R/W

Advertisement