Alarm Determination Function
• Individual alarm determination can be performed in two levels of threshold 1 and threshold 2 for the
measurement temperature of the target in the field of view of each infrared thermal sensor.
• If an individual alarm occurs in any of the infrared thermal sensors connected to the Main Unit, tran-
sistor output can be performed as a comprehensive alarm.
• With the help of the arrival prediction function of the Main Unit, it is possible to predict the tempera-
ture that will be finally reached from the temperature at the time of startup, and alarm determination
can be performed based on this predicted value.
• It is possible to monitor each measured value and the alarm status of each infrared thermal sensor
from the PLC or PC. EtherNet/IP (tag data link or CIP communications) or Modbus TCP can be used
as the communications method.
 Image of Alarm Determination Function
Threshold 1: Set as the minimum temperature at which maintenance is required (When Threshold Automatic
Setting Function of Alarm Temperature is used, the minimum temperature at which maintenance is
recommended is automatically set).
Threshold 2: Set as the minimum temperature at which urgent maintenance is required (When Threshold Automatic
Setting Function of Alarm Temperature is used, the minimum temperature at which urgent maintenance is
recommended automatically set).
Measured
object
temperature
Threshold 2
Threshold 1
Device status
*1. You can identify the status of the device from the color of the Main Unit alarm bar. You can also identify the
status of the device from the state of transistor output 1 or 2.
Settings and Monitoring by Software Tool
• A maximum of five Main Units can be connected to the software tool.
• Setting the sampling cycle in the range of 1 to 99 minutes or 1 to 99 hours from the software tool
• Displaying the thermal image of each infrared thermal sensor on the software tool
• Automatically calculating the temperature alarm threshold from the past results
• Logging the temperature data and status
• Displaying the photo image of the installation location of the K6PM-TH sensor (measurement location) *
*2. Photo images must be captured by the customer.
External Trigger Input
• It is possible to interrupt the measurement by an external trigger input (purpose: when the control
panel door is opened/closed, etc.).
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Normal
Maintenance required
Measured
temperature
Urgent maintenance required
Alarm Bar
(Green)
(Yellow)
(Red)