Main Unit Characteristics
Item
Temperature measurement range
Measurement temperature accuracy
Sampling cycle for the sensor
External
External contact input
trigger
specifications
Short circuit current
Alarm
Measurement parame-
ters
Expression method
Number of variables
Threshold setting
range
Hysteresis
Resetting method
LCD display
Display resolution
Applicable
Approved standards
standards
Conforming standards
EMC
Recommended fuse
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Degree of protection
Warranty period
Indicators
Alarm bar
MS and NS
*1. Manual resetting method: Press and hold the SEG/ALM RST Button
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Model
The temperature measurement range is described in the temperature
sensor (K6PM-THS3232) performance.
The measurement temperature accuracy is described in the temperature
sensor (K6PM-THS3232) performance.
Approx. 1 second per Unit
Short circuit: Residual voltage 1.5 V max.
Open: Leakage current 0.1 mA max.
Approx. 7 mA
Current temperature, differential temperature, sensor internal tempera-
ture
Transistor output, alarm bar display
Two threshold values per segment (Threshold 1 and Threshold 2)
0.0 to 999.9°C (0.0 to 999.9°F)
3.0°C width (5.4°F width)
*1
Manual resetting
or automatic resetting (switching)
7-segment digital displays and individual indicators
0.1°C
UL61010-1 (listing) installation location: Pollution degree 2, Korean Radio
Waves Act
RCM
EN61326-1 (EMI: Class A EMS: Industrial Location)
T2A, time lag, shut-off capacity
20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all RS-485 communications terminals, and all external trigger
input terminals, all transistor output terminals and all Ethernet ports
2,000 VAC for 1 minute
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all RS-485 communications terminals, and all external trigger
input terminals, all transistor output terminals and all Ethernet ports
Frequency: 10 to 55 Hz, 0.35-mm single amplitude in X, Y, and Z direc-
tions (10 sweeps of 5 min each)
2
150 m/s
, 3 times each in X, Y, and Z axes, 6 directions
IP20
1 year
Red, yellow, and green
Red and green
K6PM-THMD-EIP