5 Monitoring and Setting with the EtherNet/IP Communications
5-3
Monitoring and Setting Using the CIP
Message Communications and
Examples of Communications
Instructions
This section shows the contents of monitoring and setting using the CIP message communications and
examples of communications instructions.
5-3-1

Services Supported by Objects in Main Units

The services supported by the objects in Main Unit are as follows.
Object name
Main Unit monitor
object
K6PM-TH sensor moni-
tor object
K6PM-TH sensor tem-
perature monitor object
Main Unit setting object
K6PM-TH sensor alarm
setting object
Identity Object
TCP/IP Interface object
5-3-2

Main Unit Monitor Object (Class ID: 374 hex)

This object reads the Main Unit status and number of connected K6PM-TH sensors.
Service Codes
Service code
01 hex
0E hex
Class ID
Specify 374 hex.
Instance ID
Specify 01 hex.
5 - 10
Class ID
374 hex
This object reads the Main Unit status and number of connected
K6PM-TH sensors.
375 hex
This object reads the status of each sensor of the Main Unit and the cur-
rent temperature value of each segment.
376 hex
This object reads the current temperature value of each pixel of each sen-
sor of the Main Unit.
377 hex
This object writes the setting parameters (such as the existence of alarm
latch, transistor output method, enabling or disabling of "Use predicted
arrival time", etc.) of the Main Unit. Alternatively, it performs each opera-
tion instruction (such as K6PM-TH sensor registration, K6PM-TH sensor
location registration, reset of the maximum temperature of all sensors
connected to the corresponding Main Unit, etc.).
378 hex
This object writes the temperature alarm parameter of each sensor of the
Main Unit.
01 hex
This object reads the Main Unit software reset and the Main Unit identifi-
cation information, and also reads the state of the built-in EtherNet/IP
port.
F5 hex
This object reads and writes settings such as the IP address, subnet
mask, default gateway, etc.
Service name
Get_Attributes_All
Reads the values of all attributes.
Get_Attribute_Single Reads the value of the specified attribute.
Function
Description
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Supported services
Classes
Instances
Not supported
Supported
Not supported
Supported