Omron K6PM-TH User Manual page 151

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

Problems
Measure-
MS blinks red
ment val-
and running
ues are
time error is ON
not dis-
in the device
played.
status.
MS indicator is
lit red.
The current temperature is
displayed, but MS blinks red
and K6PM sensor error is
ON in the K6PM device sta-
tus.
The current temperature
value is displayed, but
"AGE" lights up.
The mea-
The measured
sured
value is fixed
value dis-
and does not
played is
change
incorrect.
Transistor
Transistor out-
put 1 or 2 does
output 1, 2
not return
during measur-
ing and moni-
toring despite
the measured
value that com-
prehensive
alarm should be
normal.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Cause
Possible correction
The hardware used
Cycle the K6PM power off and
then on.
for the replacement
time alert function
If the error still occurs, contact
may have failed.
OMRON sales or your dealer.
The Main Unit may
Turn ON the power supply to the
Main Unit again. If it still occurs,
be damaged.
contact our sales or distributor.
A K6PM-TH sensor
Return the sensor angle to its
angle deviation has
original state.
occurred.
Alternatively, perform position
adjustment and position registra-
tion.
If the event cannot be cleared
with the above action, turn ON
the power supply to the sensor
again.
This event may be cleared by
turning ON the power supply to
the sensor multiple times.
If no improvement is seen in the
event after taking the above
action, replace the sensor.
The Main Unit run-
Consider replacing the Main Unit. 4-2-1 Functions of Mon-
ning time has
reached the
approximate
replacement time.
In the case of a
Either turn ON the power again or
trigger (external
turn OFF the external trigger
trigger), the mea-
input.
sured value is held
and displayed.
Alarm latch is set
Long-press the SEG / ALMRST
to "enable"
key on the front panel of the
K6PM device for at least 5 sec-
onds to release the alarm latch.
Or, change the alarm latch setting
to None (Disabled).
7 Troubleshooting
Reference
---
4-2-1 Functions of Mon-
itoring the Temperature
in Control Panel with
the Main Unit and the
Software Tool on page
4-13
Refer to K6PM-TH sen-
sor location registration
or K6PM-TH sensor
angle deviation notifica-
tion function.
Refer to l Actions to
Take When Angle Devi-
ation Occurs on page
7-5 described later.
itoring the Temperature
in Control Panel with
the Main Unit and the
Software Tool on page
4-13
Refer to the Notification
of the Main Unit
replacement timing.
4-2-1 Functions of Mon-
itoring the Temperature
in Control Panel with
the Main Unit and the
Software Tool on page
4-13
Refer to External trigger
input of the Main Unit.
4-2-1 Functions of Mon-
itoring the Temperature
in Control Panel with
the Main Unit and the
Software Tool on page
4-13
Refer to Alarm latch of
the Main Unit.
7 - 3