Product Information; Ip Address - Omron K6PM-TH User Manual

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

6 Monitoring and Setting with the Modbus TCP
6-3-4

Product Information

Address
C000 hex
C001 hex
C002 hex
C003 hex
C004 hex
C005 hex
C007 hex
C00A hex
*1. R: Read using Reading of multiple registers (03 hex).
*2. Product code
Product code
512 (200 hex)
*3. The device revision is as follows.
Example: In the case of version 1.23
Major: 0001 hex
Minor: 0023 hex
*4. Product name is in ASCII notation.
Example: 4B 36 50 4D...hex (K6PM...)
If the name is in less than 32 characters, all the succeeding areas become 00 hex.
6-3-5

IP Address

Address
C200 hex
C202 hex
C204 hex
C206 hex
*1. R: Read using Reading of multiple registers (03 hex).
W: Write using Writing of multiple registers (10 hex).
6 - 14
Data name
Vendor ID
Device type
Product code
Device major revision
Device minor revision
Serial number
MAC address
Product name
Model
K6PM-THMD-EIP
Data name

IP address

Subnet mask
The default gateway
IP address setting method
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Data Range
002F hex
0304 hex
*2
*3
*3
Product specific
00 00 0A ** ** ** hex
*4
Data Range
Example: C0 A8 FA 1E hex
(192.168.250.30)
Default value: FF FF FF 00 hex
(255.255.255.0)
Default value: 00 00 00 00 hex
(0.0.0.0)
00000000 hex: Static IP
address.
00000001 hex: Set by BOOTP.
00000002 hex: BOOTP
one-shot.
Number of
*1
R/W
bytes
2
R
2
R
2
R
2
R
2
R
4
R
6
R
32
R
Number of
*1
R/W
bytes
4
R/W
4
R/W
4
R/W
4
R/W