Omron K6PM-TH User Manual page 161

Thermal condition monitoring device
Hide thumbs Also See for K6PM-TH:
Table of Contents

Advertisement

Symbol
Name
NS
Net-
work
Status
 Transistor Output Specifications
Name
Transistor
Threshold 1 excess output of comprehensive alarm.
Output 1
Transistor output type can be set to Normally Closed or
Normally Open.
Transistor
Threshold 2 excess output of comprehensive alarm.
output 2
Transistor output type can be set to Normally Closed or
Normally Open.
Transistor
Main Unit error and K6PM-TH sensor error output
output 3
• Normal: ON
• Main Unit error and K6PM-TH sensor error: OFF
The output type of transistor output 3 is fixed as Nor-
mally closed.
*1. The Main Unit error and K6PM-TH sensor error specify any one of the following:
• Main Unit internal error (internal CPU error or internal memory error)
• K6PM-TH sensor communications error or sensor type error
• The detection of the K6PM-TH sensor angle deviation
• Temperature measurement range exceeded
• Running time error
*2. The operation of transistor output 3 is as described below.
Status of Main Unit
Operating
Main Unit internal error
In monitoring mode
K6PM-TH sensor search mode or
K6PM-TH sensor position adjust-
ment mode
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
Color
Status
Green
Lit
Flashes at 1-s
intervals
Red
Lit.
Flashes at 1-s
intervals
---
Not lit
Status
Before data acquisition
Normal
K6PM-TH sensor communications error or sensor type
error
The detection of the K6PM-TH sensor angle deviation
Temperature measurement range exceeded
Running time error
Before data acquisition
Normal
K6PM-TH sensor communications error or sensor type
error
The detection of the K6PM-TH sensor angle deviation
Temperature measurement range exceeded
Running time error
Operating condition
Tag data link or message connection established
No tag data link or message connection established
IP address duplication status
The connection has timed out
No power supply, or IP address not set
Description
If threshold 1 exceeded occurs for the
comprehensive alarm, transistor output 1
remains OFF and transistor output 2
remains ON.
If threshold 2 exceeded occurs for the
comprehensive alarm, both transistor out-
put 1 and transistor output 2 turn OFF.
(Normally closed type)
*1
*2
Status of infrared thermal sensor
Appendices
A
Transistor
output 3
OFF
ON
OFF
ON
OFF
A - 5