Omron OMNUC W Series Manual page 236

Devicenet option unit
Hide thumbs Also See for OMNUC W Series:
Table of Contents

Advertisement

A.96
A.96: Communications Warning
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ALO2
OFF
ON
Note OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During DeviceNet
communications
Cause
A
Cable and connector contact is faulty.
B
Malfunction due to noise.
A.98
A.98: Main Power OFF
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ALO2
OFF
OFF
Note OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
When main power supply
OFF
Cause
A
Power supply cable and the connector con-
tact is faulty.
B
Power Supply Unit is defective.
9-25
9.3 Troubleshooting with Alarm Displays
ALM Output
ALO3
ON
ON
A, B
Correct the connector wiring.
Take noise prevention measures.
ALM Output
ALO3
OFF
ON
A, B
Correct the connector wiring
Check the Power Supply Unit.
Remedy
Remedy
.