Omron OMNUC W Series Manual page 144

Devicenet option unit
Hide thumbs Also See for OMNUC W Series:
Table of Contents

Advertisement

Command Method
1. Set the Servo ON Command (byte 0, bit 1) to 1.
2. Set the movement direction (byte 3, bit 1).
The movement direction setting is disabled when the Pn853 setting is 1 (travel the short-
est distance).
3. Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified,
set the value corresponding to (target station number) - (present station number) in bytes
4 to 7.
4. Set the target station number.
5. Set the Station Command (byte 2, bit 5) to 1.
Note When a relative value is specified, set the station number "n" so that the following formula is
satisfied:
The movement amount per station
Byte
Bit 7
Bit 6
0
0
0
Response type
1
0
0
2
0
0
3
4
5
6
7
6.6 Details on Move Commands for Remote I/O Communications
Station 0
Station 1
Station 2
×
station number "n"
99,999,999
Bit 5
Bit 4
Bit 3
0
1
0
1
0
0
0
0
0
Target station number
6-47
Bit 2
Bit 1
Bit 0
0
1
0
0 Hex
0
0
0
0
DIR
INC
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Omnuc w r88a-ncw152-drt

Table of Contents