SBR.E - Enabling SBR error

Acronym
SBR.E
INPUT.1 (or INPUT.2) SBR ENABLE
Enables open thermocouple probe error detection, also permitting infrared sensor management with maximum 4Kohm
output impedance.
This parameter only appears when a thermocouple type input is selected.
When OFF, the parameter will be forced to ON (see options) at each Power On
Unit of measurement:
Options:
OFF = Disable SBR alarm
On = Enable SBR alarm
On.t = Enable SBR alarm with timing
TYPE 3
20MA
= Sensor 0...20 mA
4-20M
= Sensor 4...20 mA
10V
= Sensor 0...10 V
2-10V
= Sensor 2...10 V
5V
= Sensor 0...5 V
1-5V
= Sensor 1...5 V
2.4VHI
= Sensor 0...2.4V high impedance
1.2VHI
= Sensor 0...1.2V high impedance
1VHI
= Sensor 0...1V high impedance
C.20MA
= Sensor 0...20 mA with custom calibration
C.4-20
= Sensor 4...20 mA with custom calibration
C.10V
= Sensor 0...10 V with custom calibration
C.2-10
= Sensor 2...10 V with custom calibration
C.5V
= Sensor 0...5 V with custom calibration
C.1-5V
= Sensor 1...5 V with custom calibration
C2.4VH
= Sensor 0...2.4 V high impedance with custom calibration
C1.2VH
= Sensor 0...1.2 V high impedance with custom calibration
Scrolling message
-
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 89
Submenu
Attributes
INPUT
R W