4.9.12. OF.SCL - Scale offset correction

Acronym
OF.SCL
INPUT.1 (or INPUT.2 or INPUT.3) INPUT OFFSET
The parameter shows and sets the offset applied to the value read in input to make it correspond to the expected value
for a certain temperature. It corrects any constant read error of the sensor.
This offset is applied linearly to all reads; therefore it cannot be used to correct any sensor linearity errors.
Unit of measurement:
Options:
-999...999

4.9.13. LO.SP - Lower limit for setpoint

Acronym
LO.SP
INPUT.1 (or INPUT.2 or INPUT.3) LOW LIMIT FOR SETPOINT
The parameter shows and sets the lower limit for defining the setpoint, i.e., the minimum value for setting a setpoint.
The scale limit is ignored if the setpoint is assigned to an MFB output (or calculated by an MFB).
Unit of measurement:
Options:
LO.SCL...HI.SCL

4.9.14. HI.SP - Upper limit for setpoint

Acronym
HI.SP
INPUT.1 (or INPUT.2) HIGH LIMIT FOR SETPOINT
The parameter shows and sets the upper limit for defining the setpoint, i.e., the maximum value for setting a setpoint.
The lower value of HI.SP is limited by the value of LO.SP.
The scale limit is ignored if the setpoint is assigned to an MFB output (or calculated by an MFB).
Unit of measurement:
Options:
LO.SP...HI.SCL

4.9.15. LO.AL - Lower limit for alarms

Acronym
LO.AL
INPUT.1 (or INPUT.2 or INPUT.3 ) LOW LIMIT FOR ABSOLUTE ALARMS
The parameter shows and sets the lower limit for defining alarms, i.e., the minimum value for setting an alarm.
Unit of measurement:
Options:
-1999...9999

4.9.16. HI.AL - Upper limit for alarms

Acronym
HI.AL
INPUT.1 (or INPUT.2 or INPUT.3) HIGH LIMIT FOR ABSOLUTE ALARMS
The parameter shows and sets the upper limit for defining alarms, i.e., the maximum value for setting an alarm.
Unit of measurement:
Options:
-1999...9999
Scrolling message
The one set with the Unit parameter
Scrolling message
The one set with the Unit parameter
Scrolling message
The one set with the Unit parameter
Scrolling message
The one used for the alarm limit.
Scrolling message
The one used for the alarm limit.
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 94
Submenu
Attributes
INPUT
R W
Submenu
Attributes
INPUT
R W
Submenu
Attributes
INPUT
R W
Submenu
Attributes
INPUT
R W
Submenu
Attributes
INPUT
R W

Advertisement

Table of Contents
loading

This manual is also suitable for:

16501850

Table of Contents