4.18.2. OUT.N - Selecting the output
Acronym
OUT.N
OUTPUT NUMBER
The parameter shows and sets the identifying number of the output to be configured.
Unit of measurement:
Options:
1...4
4.18.3. STAT - Defining the output state
Acronym
StAt
OUTPU.1 (o OUTPU.2... OUTPU.4) DIGITAL OUTPUT STATUS
The parameter shows and sets the state of the output with identifying number "x".
The active direct output corresponds to the relay, logic, or trial output ON (conducting).
The active inverse output corresponds to the relay, logic, or trial output OFF.
If the output is continuous, direct corresponds to minimum = 4mA and maximum = 20 mA, while inverse corresponds to
minimum = 20 mA and maximum = 4 mA.
The outputs can be forced so that they are always on or off.
On models 1650-1850, if the VT1, option is present, the parameter is ON.
Unit of measurement:
Options:
DIREC
INVRS
OFF
ON
DI.PWM = Direct output with partialisation of ON/OFF and cycle time CY.TIM (for Output 1 of
CONT.A or CONT.C type only)
IN.PWM = Direct output with partialisation of ON/OFF and cycle time CY.TIM (for Output 1 of
CONT.A or CONT.C type only)
Scrolling message
Number
Scrolling message
-
= Direct output
= Inverse output
= Output forced off
= Output forced on
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 134
Submenu
Attributes
OUTPU
R W
Submenu
Attributes
OUTPU
R W