Installation; Mounting The Controller; General Installation Rules; Drilling Dimensions - gefran 850 Installation And Instruction Manual

Double pid temperature controller
Table of Contents

Advertisement

Attention! The devices described in this manual must be installed by trained personnel in conformity to
current laws and regulations, following all of the instructions in this manual.
Before installing, check that the controller is in perfect condition and was not damaged in shipment. Make
sure that the package contains all of the accessories listed on the accompanying document, especially the
gasket and the fastening brackets.
Check that the order code matches the configuration required for the intended application (supply voltage,
number and type of inputs and outputs). See Chapter 10 - Ordering code - to check the configuration cor-
responding to each order code.
Attention! If even one of the requirements mentioned above (trained technician in, device in perfect condi-
tion, correct configuration) is not satisfied, interrupt the installation and contact your Gefran dealer or Gefran
Customer Service.
2.1.

Mounting the controller

2.1.1.

General installation rules

The controller is designed for permanent indoor installation.
It must be mounted on electrical panels or on panels con-
trolling machines or production process plants that are able
to protect the exposed terminals on the rear of the controller.
Attention! DO NOT install the controller in a
potentially inflammable or explosive atmosphere.
It can be connected to elements that work in
such atmospheres only by means of appropriate
interfaces that conform to safety regulations in
force in the country of installation.
Attention! the controller is used in applications with
risk of harm/damage to persons/property, it MUST
be connected to dedicated alarm devices.
It is advisable to provide the possibility, during
normal functioning of the controller and of the
system or equipment that it controls, of checking
whether any alarms have tripped.
The controller must be installed in a location that is not
subject to sudden temperature changes or to freezing or
condensation, and no corrosive gases must be present.
The controller can work in Pollution Degree 2 environments
(presence
of
non-conductive
conductive due to possible condensation).
Do not allow scrap or metal particles from machining or
condensation products to reach the device.
The controller is sensitive to strong electromagnetic fields.
Do not position it near radio devices or other equipment
that may generate electromagnetic fields, such as power
contactors, relays, thyristor power units (especially phase
angle), motors, solenoids, transformers, high-frequency
welders, etc.
2.

INSTALLATION

dust,
only
temporarily
80209C_MHW_850-1650-1850_20-2020_ENG_pag. 21
2.1.2.

Drilling dimensions

For correct installation, respect the dimensions of each hole
and the distance between adjacent holes shown in the figures
for each model (Figure 2 - 850 drilling dimensions and tem-
plates
14, Figure 4 - 1650 drilling dimensions and tem-
plates
17, Figure 6 - 1850 drilling dimensions and tem-
plates
20).
Attention! The support on which the operator
panel is mounted must:
be sufficiently rigid and robust to support the
device without bending during use;
be from 1 to 4 mm thick to allow the device to
be fastened with the supplied bracket.
2.1.3.

Protection against infiltration of dust

and water
The front of the controller has an IP65 protection index, so
the device can be installed without problems in rooms that
are very dusty or subject to splashing water provided:
the housing in which the device is inserted is dust-tight
and watertight;
the support on which the device is installed is perfectly
smooth and without undulations on the front;
the hole on the support scrupulously respects the
specified drilling dimensions;
the device is fully tightened to the support to ensure that
the gasket inserted between the device and the panel is
watertight
Attention! If not adequately protected, the con-
troller has an IP20 protection index (rear container
and terminal board.