H.pb - Proportional Heating Band Or Hysteresis In On-Off Control; H.it - Integral Heating Time; H.dt - Derivative Heating Time; H.p.hi - Maximum Limit Of Heating Power - gefran 850 Installation And Instruction Manual

Double pid temperature controller
Table of Contents

Advertisement

4.14.10. H.PB - Proportional heating band or hysteresis in ON-OFF control

Acronym
H.PB
PID.1 (or PID.2) HEATING PROPORTIONAL BAND OR ON/OFF HYST
The parameter shows and sets the proportional heating band or hysteresis in the ON-OFF control, calculated as a percent-
age of full scale of the main or auxiliary input.
Unit of measurement:
Options:
0.0...999.9

4.14.11. H.IT - Integral heating time

Acronym
H.IT
PID.1 (or PID.2) HEATING INTEGRAL TIME
The parameter shows and sets the integral heating time.
Unit of measurement:
Options:
0.00...99.99

4.14.12. H.DT - Derivative heating time

Acronym
H.DT
PID.1 (or PID.2) HEATING DERIVATIVE TIME
The parameter shows and sets the derivative heating time.
Unit of measurement:
Options:
0.00...99.99

4.14.13. H.P.HI - Maximum limit of heating power

Acronym
H.P.HI
PID.1 (or PID.2) HEATING POWER HIGH LIMIT
The parameter shows and sets the maximum limit of heating power.
Unit of measurement:
Options:
0.0...100.0

4.14.14. H.P.LO - Minimum limit of heating power

Acronym
H.P.LO
PID.1 (or PID.2) HEATING POWER LOW LIMIT
The parameter shows and sets the minimum limit of heating power.
Not available for dual action. The power of PID heating/cooling control (called dual action) is limited by the values of
H.P.HI and C.P.HI.
Unit of measurement:
Options:
0.0...100.0
Scrolling message
%
Scrolling message
Minutes
Scrolling message
Minutes
Scrolling message
%
Scrolling message
%
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 117
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W