4.30. Submenu LINRZ - Configuring custom linearization

Acronym
Scrolling message
LINRZ
CUSTOM
LINEARIZATION CONFIG

4.30.1. LNRZ.N - Selecting custom linearization

Acronym
LNRZ.N
CUSTOM LINEARIZATION NUMBER
The parameter shows and sets the identifying number of the custom linearization to be configured.
Unit of measurement:
Options:
1...2

4.30.2. STP.xx - Value of step xx

Acronym
STP.xx
LINRZ.1 (o LINRZ.2) CUSTOM LINEARIZATION STEP
The parameter shows and sets the value of the various steps, with xx from 0 to 32.
The start scale value goes in STP.00 and the full-scale value in STP.32.
The value of the nth step corresponds to the input: mV start scale + n*ΔmV con ΔmV = (mV full scale - mV start scale)/32.
Unit of measurement:
Options:
-1999...9999
Password
Level 2
Parameter
Selecting custom
LNRZ.N
linearization
VValue of step xx
STP.xx
Setting mV at start of
MV.STA
scale
Setting mV at
MV.fUL
full scale
Setting mV at
MV.50C
temperature of 50°C
Scrolling message
Number
Scrolling message
Scale points
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 185
Description
Lets you configure the parameters for custom linearization in
32 steps or 4 points.
The submenu is visible only if custom linearization was
enabled in the configuration of the main input or of the auxi-
liary input.