4.9.8.

FILT.D - Digital filter on PV display

Acronym
FILT.D
INPUT.1 (or INPUT.2 or INPUT.3) DIGITAL FILTER ON DISPLAY PV
The parameter shows and sets the allowed tolerance between the real PV value and the value on the PV display: if the
variation in real PV is within the interval displayed value - FILT.D... displayed value + FILT.D the displayed value does not
change. With 0.00 no filter is applied..
Unit of measurement:
Options:
0.0...9.9
4.9.9.

DEC.P - Number of decimals displayed

Acronym
DEC.P
INPUT.1 (or INPUT.2 or INPUT.3) DECIMAL POINT POSITION
The parameter shows and sets the decimal point position for the process value (PV) displayed, i.e., defines its number of
decimal figures.
The number of decimal set may reduce the limits of the measurement scale used.
Unit of measurement:
Options:
0...3
0 / 1
Scrolling message
The one set with the Unit parameter
Scrolling message
Number
= Number of decimals displayed
= Number of decimals displayed, only for TC and RTD sensors